ICP DAS FR-32P/DIN - 32 points isolated digital input module by ICP DAS
|
|
|
32-channel FRNet Isolated Digital Input Module
|
|
|
The FR-2156T has 8-channels isolated photo-coupler output and the transfer speed is fixed at 1M bps. The default signal connector of FR-2156T is a 12-pin 0.15” screw terminal connector.
According to different applications, the users can choose suitable modules. The FR-2100 I/O module has a FRNet interface. The users can daisy chain several FR-2100 modules together. Via FRNet, the FR-2100 modules can extend the discrete I/O control of PC and PAC easily. For further information about the networking of FR-2100 series; please refer to literature related to I-7188EF, I-8172, FRB-200
- Built-in Wire-saving FRnet DI/DO control
- High-speed transmission reliability
- Simple synchronization mechanism
- No software overhead on protocol processing
- Supporting broadcasting (1:n data transmission)
- Duplicating output easily
- Fixed I/O scan-time and I/O synchronization
- DIN-Rail mountable
- Industrial Automation
- Remote I/O control
- Wire-saving application
- Built-in Wire-saving FRnet DI/DO control
Product Information |
Communication speed |
250K bps |
Communication distance |
400m max |
Number of channels |
32 |
Input low voltage |
0 ~ +/-1V |
Input high voltage |
3.5 VDC ~ 30 VDC |
Input impedance |
3K; 1/4W |
Response time |
1 KHz max |
Power Requirement |
10~30V |
Wire cable |
CPEV 0.9S (2P Twisted-pair wire) |
Power consumption |
24V@140mA(max) |
Operating temperature |
-25°C ~ +75°C |
Operating humidity |
10% ~ 90% RH, non-condensing |
Storage temperature |
-30°C ~ +85°C |
Storage humidity |
5% ~ 95% RH, non-condensing |
Dimensions |
173 mm x 117 mm |
- Built-in FRnet interface
- Real I/O synchronization
- Innovative token-stream technology
- Support Broadcasting
- Real Deterministic Control
- Fixed Scan time: 256 points @ 2.88 ms
- Each bank consists of 8 input channels and has its own ground reference
- ASIC design without CPU
- Memory-map I/O
- No protocol and no software overhead
- Easy Programming and OS-independent
- Din-rail mounting
- Two-Wire Cabling
- Jumper setting
- Interface circuit
|
|
|
|